1. HP reducing station with directly mounted pneumatic actuator
Type ADUV-100-350-60
Body shape: Angle shape
Nominal size: DN100/DN350
Nominal pressure rating: PN160 / PN16
Overall lengths
Inlet: 300 mm, outlet: 700 m
Material: 13CrMo44 / P235GH
Connections
Inlet: Weld end DN100 / PN160, D. 114.3 x 6.3 mm
Outlet: Weld end DN350 / PN16, D. 355.6 x 5.6 mm
Water: Flange DN25 PN16
Dimensioning
Pressure: Inlet 75bar, outlet 9.1 bar
Temperature: inlet 480°C, outlet 410 °C
Test pressure: inlet 240bar, outlet 24bar
Differential pressure for actuator design: 75 bar
Relief over 5 stages
Seat diameter: 65 mm
Stroke: 45 mm
KVS: 42.5 m³/h
2. Water control valve in angle and flange design
Type AWRV-25-25-12-PN16
according to dimension sheet 9.2003.3820.11.1M
Nominal size: DN25
Leg length: 115 mm
Material
Body P250GH (1.0460)
Inlet P250GH (1.0460)
Outlet P250GH (1.0460)
Inlet: Flange DN 25 / PN 16
Outlet: Flange DN 25 / PN 16
with pneumatic actuator
3. Turbine bypass station / HP steam conversion stationwith
directly mounted pneumatic actuator
Type ADUV-100-1000-60
Body shape: Angle shape
Nominal size: DN100/DN1000
Overall lengths
Inlet: 325 mm, outlet: 1350 mm
Material: 13CrMo44 / P235GH
Connections
Inlet: Weld end DN100 PN160, D: 114.3 x 6.3 mm
Outlet: Weld end DN1000 PN16, D. 1016 x 10.0 mm
Water: Flange DN25 PN16
Dimensioning
Pressure: inlet 75 bar, outlet 1.5 bar
Temperature: inlet 480°C, outlet 120°C
Test pressure: inlet 240bar, outlet 24bar
Differential pressure for actuator design: 69 bar
Relief via 8 stages
Seat diameter: 65 mm
Stroke: 45 mm
KVS: 38 m³/h
with pneumatic actuator
4. Water control valve in angle and flange design
Type AWRV-25-25-18-PN16
according to dimension sheet 9.2003.3820.21.1M
Nominal size: DN25
Leg length: 115 mm
Material
Body P250GH (1.0460)
Inlet P250GH (1.0460)
Outlet P250GH (1.0460)
Inlet: Flange DN 25 / PN 16
Outlet: Flange DN 25 / PN 16
with pneumatic actuator