Type AKS-150-150-140-PN160
DN 150 / PN 160 / 1.7335
Nominal pressure: PN 160
Nominal size: DN 150
Body material: 13CrMo44 (1.7335)
Seat diameter: 140 mm
Calculation pressures: 86 bar
Calculation temperatures: 510 °C
Test pressures for pressure test: 240 bar
Differential pressure for actuator sizing: 80 bar
Reducing station R5 10-6bar track
Type ADUV-250-250-150 Straight-through body design Body Material GP240GH (1.0619) Flange design Water connection Material P250GH (1.0460) Design parameters 25 bar / 250 °C Seat: Ø…